Call Us

773-774-8616

Monday to Friday

7:00am - 5:00pm CST

Email Us

info@heinleinsupply.com

Loren Cook KSP

Loren Cook

Loren Cook KSP Kitchen Supply Fan Belt & Direct Drive

The Loren Cook KSP is a filtered, forward curved centrifugal kitchen supply fan available in belt drive (KSPB) and direct drive (KSPD) configurations. All KSP units are roof curb mounted with side or bottom discharge and ship with washable aluminum filters. Call us for sizing help, lead time, or pricing on any KSP model.

Drive Type Available Sizes CFM Range Max Static Pressure
KSPB (Belt Drive) 90, 100, 120, 150, 180, 200 400 – 12,000 1.75″
KSPD (Direct Drive) 94–99, 103–106, 122–127 100 – 1,800 0.75″

The KSP line is designed to meet NFPA 96 fresh air requirements when paired with the correct Loren Cook exhaust fan and accessories. All units are UL 705 and cUL 705 listed, AMCA certified, and manufactured at an ISO 9001 certified facility in Springfield, Missouri.

Warranty claims and returns are processed directly through your authorized Loren Cook distributor, Heinlein Supply.

Share this
Email
Facebook
Print

KSP Housing and Filter Construction

The housing is minimum 18 gauge galvanized steel bolted to a minimum 16 gauge steel base with pre-punched mounting holes and a 3-inch integral skirt. All fasteners are corrosion resistant. The insulated top cover uses quick-release latches for tool-free access to the motor and drive components.

Every KSP ships with one-inch permanent washable aluminum filters standard. Two-inch washable aluminum filters are available as an option. The intake hood includes reinforcing cross breaks to prevent drumming.

KSPB Belt Drive Components

The KSPB blower assembly sits on rubber vibration isolators. The motor is NEMA B with class B insulation, rated for continuous duty. Bearings on sizes 90 through 180 are permanently lubricated sealed ball type selected for a minimum L50 life of 200,000 hours. Size 200 uses heavy duty regreasable ball bearings in a cast iron housing with the same L50 rating.

Belts are oil and heat resistant, non-static type. Drives are precision machined cast iron, keyed to both the wheel and motor shafts, and sized for 150 percent of installed motor horsepower. The variable pitch motor drive is factory set to the specified fan RPM. The wheel is a forward curved DWDI centrifugal type made of painted steel, balanced per AMCA Standard 204-05.

KSPD Direct Drive Components

The KSPD uses an open drip-proof motor with permanently lubricated sealed bearings and built-in thermal overload protection. The motor assembly is mounted on rubber vibration isolators. The KSPD covers three cabinet sizes and is suited for lower-volume kitchen supply applications where belt drive maintenance is not practical.

KSPB Cabinet Dimensions by Size

Size Cabinet (Sq.) Height Roof Opening (Sq.) Discharge Opening Ship Weight
90 24-11/16″ 24″ 19-1/2″ 10-1/8 x 11-9/16 183 lbs
100 28-11/16″ 27″ 23-1/2″ 11-1/4 x 12-7/8 218 lbs
120 32-11/16″ 32-1/4″ 27-1/2″ 13-5/16 x 15-3/8 253 lbs
150 32-11/16″ 37-7/8″ 27-1/2″ 15-3/4 x 18-3/8 327 lbs
180 36-11/16″ 41-7/16″ 31-1/2″ 18-3/4 x 21-5/8 392 lbs
200 48-11/16″ 49-7/16″ 43-1/2″ 24-7/8 x 24-3/4 589 lbs

NFPA 96 Installation with KSP and VCR

The KSP meets NFPA 96 fresh air requirements when installed with a Loren Cook VCR exhaust fan on a common curb cap. The VCR mounts on one side with a hinged base, vented extension, and grease collection device. The KSP mounts on the other side with an intake extension.

NFPA 96 requires the exhaust fan outlet to sit a minimum of 40 inches above the roof surface, with the supply fan intake at least 10 feet from the exhaust outlet. Where 10 feet of horizontal separation is not possible, a 3-foot minimum vertical separation with a special extended vented extension is acceptable. Call us with your roof dimensions and exhaust fan model to confirm the correct common curb, intake extension, and accessory configuration.

FAQ

What is the difference between the KSPB and KSPD?

The KSPB is belt drive with six sizes covering 400 to 12,000 CFM. The KSPD is direct drive with three cabinet sizes covering 100 to 1,800 CFM. Belt drive gives more flexibility in motor selection and speed adjustment. Direct drive eliminates belt maintenance for smaller applications.

Can the KSP be ordered with side discharge?

Yes. Side discharge is a factory option on all KSP sizes. Cabinet and curb dimensions are the same for both discharge directions. Specify side or bottom discharge at the time of order.

What speed control options are available?

The KSP supports FSC, VFD, Vari-Flow, and SimpliDrive speed control options. Motor types include AC and EC.

Call us to match the right control to your application.

Related Products


Loren Cook Units Browse All
›


Loren Cook Serial Number Lookup Browse All
›


ACED / ACEB Exhaust Fans Browse All
›

Request Current Inventory and Pricing

Same-day shipping is available for in-stock orders placed before 3:00 PM. If the unit or part you need is not listed online, call us for current availability.

Contact us for Loren Cook KSP information

Fill out the contact form below. The more information, such as shipping location and model number, the more accurate the quote will be.

Our team will review your request and send you a quote or information as soon as possible.

We hate spam, too.

Your information is only used for us to contact you regarding your inquiry.